Table 2

Approved Meter Service Devices

(print from .pdf)

Effective September 4, 2020
Updates All Previous Tables

Single Phase, Single Position
Underground Entrance
200 or 400 Amp, 120/240 or 208/120 Volt
4 or 5 Terminal

MFG. & CATALOG # 5TH TERMINAL ACCESSORY IF REQUIRED SERVICE AMPS DIMENSIONS (INCHES) TERMINAL SIZE (AWG OR KCMIL) BYPASS TYPE
(See Note #2) MIN. MAX
CUTLER HAMMER
1004884A-CH ARP00035CHJ 200 13 x 13 x 5 8 350 Horn
1004984A-CH ARP00326CH 400
(Cl 320)
365/8 x 15 x 6 See Note #9 Lever
DURHAM (See Note #8)
1004884A ARP00035 200 13x13x5 8 350 Horn
1004984A ARP00326 400
(Cl 320)
365/8 x 15 x 6 See Note #9 Lever
MIDWEST
1004884A-MEP ARP00035MEP 200 13 x 13 x 5 8 350 Horn
1004984A-MEP ARP00326MEP 400
(Cl 320)
365/8 x 15 x 6 See Note #9 Lever
MILBANK
U1980-0-KK-BL K5T 200 151/2 x 13 x 41/2 2 350 Horn
U4413-0-KK K5T 200 151/4x13x41/2 2 350 Horn
U3939-X ----------- 400
(Cl 320)
30 x 153/4x 53/4 See Note #9 Lever
U3126-0-KK-BLG K5T 200 151/2 x 13 x 41/2 2 350 Horn
MURRAY
RL199A RX112FJ 200 14 x 13 x 5 6 350 Horn
RL199CJ RX112FJ 200 14 x 13 x 5 6 350 Horn
SIEMENS
SUAS817-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
SUAS877-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
S44704-82 ----------- 400
(Cl 320)
34 x 20 x 6 See Note #9 Lever
S44704-82PP ----------- 400
(Cl 320)
34 x 20 x 6 See Note #9 Lever
SQUARE D
1004984A-SQD ARP00326SQD 400
(Cl 320)
365/8 x 15 x 6 See Note #9 Lever
TALON (formerly Landis + Gyr (L+G)) (See Notes #7 & #8)
UAS817-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
HUAS817-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
UAS877-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
HUAS877-PPGP 659-0121 200 14 x 13 x 5 6 350 Horn
1004984A ----------- 400
(Cl 320)
281/2 x 15 x 6 See Note #9 Lever
44704-82 ----------- 400
(Cl 320)
34 x 20 x 6 See Note #9 Lever
44704-82PP ----------- 400
(Cl 320)
34 x 20 x 6 See Note #9 Lever

MOST RECENT CHANGES

DATE MFG. CATALOG # STATUS REASON
09/2020  Milbank U3939-X Updated Model No. updated by Milbank
08/2019 Square D 1004884A-SQD Removed No longer made

NOTES:

  1. All meter bases listed in this table are "ringless" style. Horn bypasses are required in all ringless bases. Class 320 bases must contain a lever bypass rated 100% continuous duty.
  2. Meter bases used for 208/120 volt, 3 wire services must have a 5th terminal installed in the 9 o'clock position. The catalog number for the 5th terminal is listed in the "5th Terminal Accessory" column in the table and must be specified when purchasing the meter base.
  3. The manufacturer's catalog number must be stamped on the outside of the meter base so that it will be visible after the base is installed. The number must not be stamped on the cover.
  4. When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer.
  5. The line (utility) terminals in all UG bases must be offset to the left or right of the socket to accommodate the installation of underground service wires.
  6. Conduit Requirements:
    200 Amp Service
    The conduit KO directly under the line (utility) terminals must accept a 3 inch conduit.
    400 Amp (Cl 320) Service
    The conduit KO directly under the line (utility) terminals must accept a 4 inch conduit. The conduit KOs directly under the load terminals must accept two (2) 3 1/2 inch conduits.
  7. Prefix "H" on Talon (formerly L&G) bases indicates bases that are sold through national retailers.
  8. Talon (formerly L&G) Underground Base #UAS817-PPG and HUAS817-PPGP has line terminals mounted on right side of base. Durham UG Base #1004884 is available with line terminals mounted on right or left side of base (specify when ordering). All other bases have line terminals mounted on left side of base.
  9. Class 320 Meter Bases:
    • All 320 amp meter bases contain stud terminals.
    • Only UL approved lay-in or box style connectors suitable for use with copper or aluminum conductors can be installed for wire termination on the studs.
    • Compression connectors are not permitted.

    CLASS 320 METER BASE
    CONNECTOR REQUIREMENTS

      Line Side Terminals Line Side Neutral Terminals Load Side Terminals
    WIRE RANGE Single Only #350 - 750 Kcmil 4/0 Awg to 500 Kcmil Single--Up to 600 Kcmil Double--Up to 350 Kcmil

    APPROVED CONNECTORS FOR
    CLASS 320 METER BASES

    MFG. Line Side Terminals & Wire Range Line Side Neutral Terminals & Wire Range Load Side Terminals
    CUTLER HAMMER ARP00129CH
    # 4 - 600 Kcmil
    ARP00129CH
    # 4 - 600 Kcmil
    Single - ARP00129CH
    Double - ARP00427CH
    DURHAM ARP00129
    # 4 - 600 Kcmil
    ARP00129
    # 4 - 600 Kcmil
    Single - ARP00129
    Double - ARP00427
    MIDWEST ARP00129MEP
    # 4 - 600 Kcmil
    ARP00129MEP
    # 4 - 600 Kcmil
    Single - ARP00129MEP
    Double - ARP00427MEP
    MILBANK *K3863 or K1540
    350-800 Kcmil
    # 2-600 Kcmil
    K1540
    # 2-600 Kcmil
    Single - K1540
    Double - K1350
    SQUARE D ARP00129SQD
    # 4 - 600 Kcmil
    ARP00129SQD
    # 4 - 600 Kcmil
    Single - ARP00129SQD
    Double - ARP00427SQD
    TALON (formerly L&G) / SIEMENS 56476
    # 3/0-800 Kcmil
    60162
    # 4/0-600 Kcmil
    Single - 60162
    Double - 56732
  10. All meter bases listed in this table are rated 600 volts AC unless otherwise noted.

* Connector size must be selected to accommodate PPL service lateral size