Table 5

Approved Instrument Transformer Cabinets

(print from .pdf)

Effective June 10, 2020
Updates All Previous Tables

72" H x 48" W X 12" D
Indoor Mounting
NEMA 1 (General Purpose)
Three Phase, 208Y/120 Volt or 240/120 Volt Delta
2000 Ampere Maximum

MANUFACTURER CATALOG #
AUSTIN COMPANY AB724812CTD/PPL
COOPER B-LINE 724812 PENN CT
E-BOX EB724812P
EAST COAST PANELBOARD PP-724812
K&S/MECO K1272
NJ SULLIVAN  PPLCT201 
UNITY MFG. CO. TR487212DDCT1
WIEGMANN N1724812-CTPPL

MOST RECENT CHANGES

DATE MFG. CATALOG # STATUS REASON
06/2020  NJ Sullivan   PPLCT201    K&S/MECO are no longer in business; NJ Sullivan is a viable replacement
10/2003 East Coast Panelboard PP-724812 Approved New Listing
APPLICATION: Five finger instrument transformer mounting for three phase, 208 or 240 volt.
MATERIAL: Galvannealed or galvanized steel with gray enamel finish or cold rolled steel with a UL recognized gray powder coat finish, minimum #14 gauge.

GENERAL SPECIFICATIONS

DOOR CONSTRUCTION: Double hinged doors are required. The hinges and hinge pins must be non-removable. Each door must have an internal stiffener, minimum #14 gauge.
LATCHING MECHANISM: A three point latching mechanism that secures both doors is required. The latching bars must pass through a guide that assures correct latching. The latching mechanism cannot protrude more than 1" inside the cabinet. All connection bolts must be permanently secured to prevent accidental contact of any metal part should the latching assembly fail.
LOCKING PROVISION: The latching mechanism handle must be designed to provide a locking provision in the closed position. This locking provision must accommodate a minimum 1/4" hasp. Key locking of the handle is not allowed.
CATALOG NUMBER: The catalog number (as listed by PPL) must be permanently marked on the inside of the right door.